Panduit Q1N2B1L2N30AHA0 Uživatelský manuál Strana 1

Procházejte online nebo si stáhněte Uživatelský manuál pro Výkonové distribuční jednotky (PDU) Panduit Q1N2B1L2N30AHA0. Panduit Q1N2B1L2N30AHA0 power distribution unit PDU Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - MSeries Rack PDU

Release 1.0Issue 1.0SmartZone™ Network-EnabledMSeries Rack PDUUser Manual

Strany 2

Network-Enabled M Series Rack PDU User Manual- 10 -Pre-InstallationThe Rack PDU products covered by this guide are designed to be installed within EIA

Strany 3 - Table of Contents

Network-Enabled M Series Rack PDU User Manual- 11 -InstallationBefore You BeginBefore installing your PDU, refer to the following lists to ensure that

Strany 4

Network-Enabled M Series Rack PDU User Manual- 12 -3. Ensure conductors are stripped adequately, exposing 15mm of copper.4. Conductors shall be connec

Strany 5 - Rack PDU

Network-Enabled M Series Rack PDU User Manual- 13 -Gland Size Grommet Cap TorqueM16 1.5 N-m (13 in-lb.)M20 3.0 N-m (27 in-lb.)M254.0 N-m (35 in-lb.)M3

Strany 6 - Symbol Description

Network-Enabled M Series Rack PDU User Manual- 14 -Optional AccessoriesSmartZone Environmental Sensors:l Smoke Sensorl Humidity Sensorl Water Rope Sen

Strany 7 - Equipment Overview

Network-Enabled M Series Rack PDU User Manual- 15 -Warning: For permanently connected equipment, a readily accessible disconnectdevice should be incor

Strany 8 - Model Numbers

Network-Enabled M Series Rack PDU User Manual- 16 -accordance with the instruction manual, may cause harmful interference to radio com-munications. Op

Strany 9

Network-Enabled M Series Rack PDU User Manual- 17 -MountingThere are two mounting options for Rack RDUsl Vertical Mountingl Horizontal MountingInstruc

Strany 10 - Pre-Installation

Network-Enabled M Series Rack PDU User Manual- 18 -

Strany 11 - Installation

Network-Enabled M Series Rack PDU User Manual- 19 -PDU Bracket for 4-Post Racks

Strany 12

Network-Enabled M Series Rack PDU User Manual- 2 -Copyright © 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored

Strany 13 - Gland Size Grommet Cap Torque

Network-Enabled M Series Rack PDU User Manual- 20 -PDU Bracket for 2-Post Racks

Strany 14 - Safety Precautions

Network-Enabled M Series Rack PDU User Manual- 21 -Horizontal MountingThis product is intended to be installed using the rack's RU mountings via

Strany 15

Network-Enabled M Series Rack PDU User Manual- 22 -HardwareLCD DisplayThe display shows the firmware version number, device model number, serial numbe

Strany 16 - Environmental Specifications

Network-Enabled M Series Rack PDU User Manual- 23 -Mode Button OperationBootloader StartupWhen the user presses and holds the Mode button, the Display

Strany 17 - Mounting

Network-Enabled M Series Rack PDU User Manual- 24 -The application stays in this mode for at least 5 seconds. If no button operation is detec-ted, the

Strany 18

Network-Enabled M Series Rack PDU User Manual- 25 -Graphical User InterfaceThe Panduit Network Enabled Rack PDU provides access to configuration, powe

Strany 19 - PDU Bracket for 4-Post Racks

Network-Enabled M Series Rack PDU User Manual- 26 -The default login and password are:Login:adminPassword:adminAfter successful login, the GUI opens t

Strany 20 - PDU Bracket for 2-Post Racks

Network-Enabled M Series Rack PDU User Manual- 27 -There are three modules within the GUI, each providing access to a different area withinthe PDU. Th

Strany 21 - Horizontal Mounting

Network-Enabled M Series Rack PDU User Manual- 28 -SetupWhen the setup module is selected, the following menu items appear along the left handside of

Strany 22 - Hardware

Network-Enabled M Series Rack PDU User Manual- 29 -IP ConfigurationSystem Name The name of the PDUSystem Location The location of the PDUContact Name

Strany 23 - Mode Button Operation

Network-Enabled M Series Rack PDU User Manual- 3 -Table of ContentsSmartZone™ Network-Enabled MSeries Rack PDU 5Contacting Panduit 5Symbols Used 5Equ

Strany 24 - Internal Error Notification

Network-Enabled M Series Rack PDU User Manual- 30 -The DHCP configuration (Dynamic Addressing provided by Infrastructure)l The DHCPv4 client allows th

Strany 25 - Graphical User Interface

Network-Enabled M Series Rack PDU User Manual- 31 -DHCPv6 configuration (dynamic addressing provided by infrastructure)The DHCPv6 client allows the us

Strany 26

Network-Enabled M Series Rack PDU User Manual- 32 -To choose the access method, click the corresponding radio button and enter the appro-priate Port n

Strany 27

Network-Enabled M Series Rack PDU User Manual- 33 -Both SNMPv2c and SNMPv3 protocols are supported simultaneously. You must enterthe credential infor

Strany 28 - IP Config

Network-Enabled M Series Rack PDU User Manual- 34 -Access Permission SettingsRead Only Permits the NMS to use only GET commandsRead / WritePermits the

Strany 29 - IPv4 Address Configuration

Network-Enabled M Series Rack PDU User Manual- 35 -Receive Traps Settingsrange of trapsEnabled (Incl. Auth Fails)Receive traps – causes the unit to is

Strany 30 - IPv6 Address Configuration

Network-Enabled M Series Rack PDU User Manual- 36 -SNMP Trap Text FormatOn, Information Off, Cleared, Unknown.<source-name> ::= <text> Dat

Strany 31

Network-Enabled M Series Rack PDU User Manual- 37 -The PDU GUI comes with the Administrator login predefined as:l Login:adminl Password:adminTo add ne

Strany 32 - SNMP NMS

Network-Enabled M Series Rack PDU User Manual- 38 -Email AlertsOn this page, you can edit email alert settings for traps. You may set up to 10 emailre

Strany 33

Network-Enabled M Series Rack PDU User Manual- 39 -Time SettingsThe Time Settings page allows you to view or edit the current date and time.Select the

Strany 34 - SNMP Receivers

Network-Enabled M Series Rack PDU User Manual- 4 -IPv4 Address Configuration 29The DHCP configuration (Dynamic Addressing provided by Infrastructure)

Strany 35

Network-Enabled M Series Rack PDU User Manual- 40 -l SNTP Servers - Simple Network Time Protocol synchronizes the clocks of com-puter systems over a n

Strany 36

Network-Enabled M Series Rack PDU User Manual- 41 -EventsThe View Events page shows a history of events that have occurred, along with specificdetails

Strany 37

Network-Enabled M Series Rack PDU User Manual- 42 -PreferencesDefault PageFrom the dropdown menu, select the first page you wantto open when a user lo

Strany 38 - Email Alerts

Network-Enabled M Series Rack PDU User Manual- 43 -RestartClicking the Restart option brings up the following screen:To restart the unit or restore to

Strany 39 - Time Settings

Network-Enabled M Series Rack PDU User Manual- 44 -Input SensorsWhen the Input Sensors module is selected, the following items appear along the left-h

Strany 40 - Syslog Servers

Network-Enabled M Series Rack PDU User Manual- 45 -Status IndicatorsAll thresholds within limitsUpper Control Limit reached/exceededUpper Warning Limi

Strany 41 - Preferences

Network-Enabled M Series Rack PDU User Manual- 46 -The Humidity Sensors screen displays default information as shown below.The Analog Voltage screen d

Strany 42

Network-Enabled M Series Rack PDU User Manual- 47 -Explanations of the editable fields in the drop-down menus for Temperature, Humidityand Analog Volt

Strany 43

Network-Enabled M Series Rack PDU User Manual- 48 -Defaults- Temperature, Humidity, and Analog Voltageand alarm purposes would be 42. This works in an

Strany 44 - Input Sensors

Network-Enabled M Series Rack PDU User Manual- 49 -Defaults- Open/Close ContactsNormal StateNormal state specifies the condition in which a contact is

Strany 45 - Defaults

Network-Enabled M Series Rack PDU User Manual- 5 -SmartZone™ Network-Enabled MSeriesRack PDUNetwork-Enabled M(Monitored)Series Rack PDUs integrate

Strany 46

Network-Enabled M Series Rack PDU User Manual- 50 -Defaults- Open/Close Contactsan alarm is required to persist after an input changes fromthe Normal

Strany 47

Network-Enabled M Series Rack PDU User Manual- 51 -Individual settings can be entered for each input channel. The drop-down menu optionsare identical

Strany 48

Network-Enabled M Series Rack PDU User Manual- 52 -Enter text to be displayed for each type of trap.

Strany 49

Network-Enabled M Series Rack PDU User Manual- 53 -PowerWhen the Power module is selected, the following menu items appear along the left-hand side of

Strany 50 - Configure

Network-Enabled M Series Rack PDU User Manual- 54 -Status 3-PhaseIf the device is 3-Phase, you will see the 3-Phase Status button as shown below. The

Strany 51 - Sensor Trap Text

Network-Enabled M Series Rack PDU User Manual- 55 -ConfigureThe Configure page allows you to view and configure Power Circuits. Depending onthe type o

Strany 52

Network-Enabled M Series Rack PDU User Manual- 56 -Clicking on the arrows next to each option opens a drop-down similar to the following:Explanations

Strany 53 - Branch Monitoring

Network-Enabled M Series Rack PDU User Manual- 57 -Configure Power CircuitsCircuit Name The name of the chosen circuit.Upper Control Limit The value a

Strany 54 - Thresholds

Network-Enabled M Series Rack PDU User Manual- 58 -Enter the desired text in the text box provided, and click the Save button to implementyour customi

Strany 55

Network-Enabled M Series Rack PDU User Manual- 6 -Symbol Description| ONO OFF

Strany 56

Network-Enabled M Series Rack PDU User Manual- 7 -Equipment OverviewThe power inlet/cord(s) connects the PDU to the electrical power source. On metere

Strany 57

Network-Enabled M Series Rack PDU User Manual- 8 -Letter What It RepresentsE Any numeral, 1-7, indicating the number of output circuit breakersFAny le

Strany 58

Network-Enabled M Series Rack PDU User Manual- 9 -Part NumberQ1N1B3H0A30AHA0Q1N1B3H0A30AXA0Q1N2B1J0A30AHA0Q1N2B1L2N30AHA0Q1N2B1M2M24AKA0Q1N2B1N3N30AHA